Remote Communications & Overview Displays
DSE890 MKII
DSEWebNet® / IoT Gateway - 4G (GSM/Ethernet)
REQUIRES - Combined 4G LTE (Main & Diversity) and GPS Antenna - 020-1053 if 4G Signal is Needed.
Unit also fully compatible with 2G & 3G.
The DSE890 MKII gateway communicates with a maximum of five connected DSE controllers, monitoring instrumentation and operating states. When this data changes, data is logged internally and transmitted from the gateway device to the DSEWebNet® or MQTT broker (Amazon Web Services, Google, IBM etc..).
DSEWebNet® software is accessed using an Internet browser or the dedicated app. Users are able to perform multiple tasks including: monitoring equipment, clearing alarm conditions, starting/stopping equipment and monitoring fuel levels.
To view UL Certification click here. |
85 mm x 149 mm x 51 mm (3.4” x 5.9” x 2.0”)
WEIGHT
0.23kg
PRODUCT VARIANTS
0890-04 - 890 DSEWebnet® / IoT Gateway - 4G GSM/Ethernet
Request a Quote
Product Highlights
Key Features
Key Benefits
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 36 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 8 V before dropout and supply recovers to 8 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
GSM 755 mA at 12 V
376 mA at 24 V
GSM & GPS 755 mA at 12 V
376 mA at 24 V
MAXIMUM STANDBY CURRENT
GSM 207 mA at 12 V
113 mA at 24 V
GSM & GPS 207 mA at 12 V
113 mA at 24 V
COMMUNICATIONS
USB (Single DSE Controller)RS485 (Multiple DSE Controllers)
Ethernet (Multiple DSE Controllers)
CAN* (Single DSE Controller)
*Only active for third-party MQQT brokers.
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.