Manual & Auto Start Control Modules
DSE7410 MKII
Auto Start Control Module
245 mm x 184 mm x 51 mm (9.6” x 7.2” x 2.0”)
PANEL CUTOUT SIZE
220 mm x 160 mm (8.7" x 6.3")
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.88kg
PRODUCT VARIANTS
7410-03 - 7410 MKII Auto Start Control Module
Request a Quote
Product Highlights
Key Features
Key Benefits
- Additional Features
- VAR alarms.
- Large memory capacity for integral PLC functions.
- Voltage measurement.
- kW overload alarms.
- Exercise timer.
- Multiple language options.
- Configurable timers & alarms.
- Configurable start/stop timers.
- Configurable maintenance alarms.
- Charge alternator failure alarm.
- Heated display option.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING8 V to 35 V Continuous
5 V for up to 1 Minute
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
510 mA at 12 V, 240 mA at 24 V
MAXIMUM STANDBY CURRENT
330 mA at 12 V, 160 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
INPUTS
DIGITAL INPUTS A-H
Negative Switching
ANALOGUE INPUTS A,B, E & F
Configurable as
Negative Switching Digital Input
0 V to 10 V Sensor
4mA to 20mA Sensor
Resistive Sensor
ANALOGUE INPUTS C & D
Negative Switching Digital Input
Resistive Sensor
OUTPUTS
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK UP
VOLTAGE RANGE+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.