Advanced Paralleling Gen-Set Controllers
DSEG8900
7" Colour Parallel Genset Controller
Overall (W X H X D)
305 mm x 161 mm x 45.2mm / 12” x 6.34” x 1.77”
Panel Cut-Out (W X H)
282 mm x 136 mm / 11.1” x 5.35”
Maximum Panel Thickness
8 mm / 0.31”
Request a Quote
Product Highlights
Key Features
Specification
DC Supply
5 V to 35 V DC continuous
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. Backlight will not be maintained during cranking.
985 mA at 12 V, 500 mA at 24 V
725 mA at 12 V, 370 mA at 24 V
0 V to 35 V
Yes
Voltage Measurement
Three-phase generator, Three-phase mains (utility)
15 V to 415 V (Ph to N) / 25 V to 720 V (Ph to Ph)
±1 % (±4.15 V Ph to N) / ±2 % (±14.4 V Ph to Ph)
3.5 Hz to 75 Hz
300 kΩ (Ph to N)
Current Measurement
Three phase bus or load / Single phase mains (utility)
0 A to 1 A, 0 A to 5 A
5 A
±1% (±0.01 A or ±0.05 A)
0.02 Ω
Inputs
Input A configurable: 0 Ω to 3 kΩ, 0 mA to 20 mA, 0 V to 10 V
A to G active low/high
A to I active low/high
±1 % of full-scale
±1 % of full-scale (V, A, or Ω)
Outputs
Analogue
Governor / AVR configurable -10 V to 10 V, 0 mA to 20 mA
Digital
Fuel output 15 A, Start output 15 A
Auxiliary
8 digital outputs (E to L) 2 A DC at supply voltage
Gain Voltage
0 V to 10 V, 0 V to 20 V mA configurable
Offset Voltage
0 V to 10 V, 0 V to 20 V mA configurable
Magnetic Pick-Up
0.5 V to 70 V RMS
1 Hz to 10 KHz
Better than 0.1 %
Communications
10/100 Ethernet Port
Data Storage
Programming Port
2 x fully isolated
Temperature
-30° C to +70 ° C / -22° F to +158 ° F
-40° C to +85 ° C / -40° F to +185 ° F
Dimensions
305 mm x 161 mm x 45.2mm / 12” x 6.34” x 1.77”
282 mm x 136 mm / 11.1” x 5.35”
8 mm / 0.31”
Environmental Testing Standards
Environmental Testing Standards
EMC Generic Immunity Standard for the Industrial Environment
EMC Generic Emission Standard for the Industrial Environment
Safety of Information Technology Equipment, including Electrical Business Equipment
Ab/Ae Cold Test -30 ºC
Bb/Be Dry Heat +70 ºC
Ten sweeps in each of three major axes
Db Damp Heat Cyclic 20/55 ºC at 95% RH 48 Hours
Cab Damp Heat Static 40 ºC at 93% RH 48 Hours
Three shocks in each of three major axes