Engine & Pump Control Modules (E-Series)
DSEE050
eView® Engine Display
To view UL Certification click here. |
112.5mm x 115 mm x 49 mm (4.43" x 4.53" x 1.93")
PANEL CUT OUT
80 mm / 3.15" Diameter
PRODUCT VARIANTS
E050-01 - eView® Engine Display
Request a Quote
Product Highlights
Key Features
Key Benefits
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING8 V TO 35 V continuous (5 V for up to 1 minute)
CRANKING DROPOUTS
Able to survive ) V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
300 mA at 12 V, 150 mA at 24 V
MAXIMUM STANDBY CURRENT
80 mA at 12 V, 44 mA at 24 V
INPUTS
MULTI-FUNCTIONAL INPUTS A to DConfigurable as: digital, current, voltage, resistance
0 V to 10 V
0 mA to 20 mA
0-3 kΩ
OUTPUTS
DC OUTPUTS A to C1 A continuous at supply voltage
VREF OUT
100 mA at 10 V / 5 V
OPERATING TEMPERATURE RANGE
-40 ° C to +85 ° C- 40 ° F to +185 ° F
HEATED DISPLAY OPERATING RANGE
Turns on at -25 ° C / -13 ° FTurns off at - 5 ° C / +23 ° F
STORAGE TEMPERATURE RANGE
-40 ° C to +85 ° CDIMENSIONS
OVERALL (W x H x D)112.5 mm x 115 mm x 49 mm
4.43" x 4.53" x 1.93"
PANEL CUTOUT
80 mm / 3.15" Diameter
Environmental Testing Standards
ELECTRO MAGNETIC COMPATIBILITY
BS EN 6100-6-2
Electromagnetic Compatibility (EMC) Noise Immunity
BS EN 6100-6-4
Electromagnetic Compatibility (EMC) Emission Standard
ISO 11452
Electromagnetic Compatibility - Road Vehicles
ISO 7637-3: 2016
Road Vehicles - Electrical disturbances from conduction and coupling
Part 3: Electrical transient transmission by capacitive and inductive coupling via lines other than supply lines
ELECTRICAL SAFETY
BS EN 61010
Safety Requirements for Electrical Equipment for Measurement, Control & Laboratory Use.
BS EN 61010: 2010
Part 1: General Requirements
BS EN 61010-2-030: 2010
Part 2-030: Particular Requirements for Testing Measuring Circuits
ELECTRICAL TESTS
ISO 16750-2: 2012
Road vechicles - Environmental conditions and testing for electrical and electronic equipment.
Part 2: Electrical loads
4.6.3 Starting profile
4.6.4 Load dump
CLIMATIC TESTS
EN 60068-2-30
Damp heat, cyclic upper temperature 55 ˚C
EN 60068-2-78
Damp heat, steady state test temperature
40 ˚C/93 % RH (21 Day Duration)
MECHANICAL TESTS
EN 60068-2-6
Part 2-6: Tests - Test Fc: Vibration (sinusoidal)
EN 60068-2-27
Part 2-27: Tests - Test Ea: Shock
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -40 °C (-40 °F)
BS EN 60068-2-2
Bb/Be Dry Heat +85 °C (185 °F)
CHEMICAL
ISO 16750-5
Chemical testing for electrical and electronic equipment - Road Vechicles
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP67/NEMA 6.